What trait do solar-thermal collectors, hydronic heat pumps and thermal storage tanks supplied by biomass boilers have in common?

Answer: They all perform best when coupled to distribution systems that operate at low supply water temperatures.

But that’s not what’s waiting for these renewable heat sources in most North American buildings. It’s common to encounter situations where a modern “low-temperature” hydronic heat source is to be added to an existing system that was designed to operate at a relatively high temperature such as 180° F. Trouble is sure to follow if the installer just removes the original “box” that supplied this high-temperature water and drops the new renewable-energy heat source into its place.

For example, most current-generation water-to-water and air-to-water heat pumps only can produce water temperatures in the range of 120° to 130°. If saddled to a distribution system that was sized to release design load output at 180° average water temperature, the heat pump quickly will trip off on an internal high-temperature or high-refrigerant pressure limit, which typically requires a manual reset. The existing distribution system cannot dissipate the rate of heat input from the heat pump with a water temperature that’s 50° to 60° lower than what it was designed for.

 

Moving downward

The two fundamental ways to reduce the supply water temperature of any hydronic heating system:

  1. Reduce the design load of the building envelope through improvements such as added insulation, better windows and lower air leakage.
  2. Add heat emitters to the existing system.

A combination of these two approaches also is possible.

Building envelope improvements reduce the design heating load of the building. After these improvements are made, the existing hydronic distribution system can meet the reduced design load while operating at lower supply water temperatures. The change in supply water temperature is proportional to the change in the design heating load. The new supply water temperature can be determined based on the same concepts used for outdoor reset control. It can be calculated using Formula 1:

The new supply water temperature can be determined based on the same concepts

Where:

Tnew = Supply water temperature at design load after building envelope improvements (°F)

Tin = Desired indoor air temperature (°F)

Qnew = Design heating load after building envelope improvements (Btu/h)

Qexisting = Existing design heating load (before improvements) (Btu/h)

TDe = Existing supply water temperature at design load (before improvements) (Btu/h)

For example, assume a building has a design heating load of 100,000 Btu/h, based on maintaining an interior temperature of 70°. The existing hydronic distribution system uses standard finned-tube baseboard and requires a supply water temperature of 180° at design load conditions. Also assume that improvements to the building envelope have reduced the design load from 100,000 Btu/h to 70,000 Btu/h. The new supply water temperature to the existing distribution system under design load conditions is calculated using Formula 1:

distribution system

Figure 1 shows the supply water temperature vs. outdoor temperature for the original load as well as the reduced load after the building-envelope improvements were made.

Figure 1 shows the supply water temperature vs. outdoor temperature

In this case, reducing the design heating load from 100,000 Btu/h to 70,000 Btu/h reduced the required supply water temperature from 180° to 147°. Although this certainly is an improvement, it still is substantially above what some renewable energy heat sources can consistently provide.

 

More emitters

If reducing the design heating load of the building does not lower the required water temperature to the desired value, it will be necessary to add heat emitters to the system.

If the original system used finned-tube baseboard heat emitters, it may be possible to add more of the same emitters. Another option might be to change out some existing baseboard for “high-output” baseboard. It’s also possible to add different types of heat emitters such as panel radiators, fan-coils or select areas of radiant panels.

The choice of which type of heat emitter to add will depend on several factors, including:

  1. Availability of different makes/models of heat emitters.
  2. Cost of the new heat emitters.
  3. How difficult it is to integrate the new heat emitters into the building.
  4. Aesthetic preferences.
  5. Floor coverings (in the case of radiant floor panels).
  6. Surface temperature limitations (in the case of radiant panels).
  7. The specific supply water temperature that is to supply design load output in the renovated distribution system.

 

More baseboard

Let’s proceed with the assumption that more fin-tube baseboard will be added. The following procedure can be used to calculate the amount of baseboard to be added to reduce the supply water temperature at design load to a predetermined value. It assumes the added baseboard is the same make and model as the existing baseboard. It also assumes the existing baseboard is a standard residential-grade product with nominal 2.25-inch square aluminum fins with a I=B=R-rated output of about 600 Btu/h/ft. at 200° water temperature.

Step 1: Accurately determine the building’s design heat load using Manual J or equivalent procedures.

Step 2: Determine the total length of finned-tube in the existing distribution system. Do not include the length of tubing that doesn’t have fins on it. The existing finned-tube length will be designated as Le.

Step 3: Determine the desired (lower) supply water temperature for which the system is to supply design load output. A suggested value is 120°.

Step 4: Estimate the lower average circuit water temperature by subtracting 5° to 10° from the supply water temperature determined in Step 3.

Step 5: Find the new average circuit water temperature on the horizontal axis of the graph in Figure 2. Draw a vertical line up from this point until it intersects the red curve. Draw a horizontal line from this intersection to the vertical axis of the graph and read the heat output of the finned-tube at the lower average circuit water temperature. This number is designated as qL. The green lines and numbers in Figure 2 show how qL is determined for an average circuit water temperature of 115°.

Step 6: Determine the length of baseboard to be added using Formula 2.

Determine the length

Where:

Ladded = Length of finned-tube of same make/model baseboard to be added (feet)

design load = Design heating load of building (Btu/h)

qL = Output of baseboard at the lower average circuit water temperature (Btu/h/ft.)

Le = Total existing length of baseboard in system (ft.)

Here’s an example. Assume a building has a calculated design load of 40,000 Btu/h, and its distribution system contains 120 ft. of standard residential finned-tube baseboard. It is currently heated by a conventional cast-iron boiler. The goal is to reduce the supply water temperature to 120° at design conditions using more of the same baseboard. Assume the temperature drop of the distribution system is 10°. Determine the amount of baseboard that must be added:

Assume the temperature drop of the distribution system is 10°

Solution

Step 1: The design load has been calculated as 40,000 Btu/h.

Step 2: The total amount of finned-tube in the system is 120 feet

Step 3: The lower supply water temperature at design load will be 120°.

Step 4: The lower average circuit water temperature will be 120° - (10/2) = 115°.

Step 5: The output of the finned-tube at an average circuit water temperature of 115° is determined from Figure 6-10 as 146 Btu/h/ft.

Step 6: The required additional length of baseboard is now calculated using Formula 2:

The required additional length

Although it might be possible to add 154 feet of baseboard to the system, it would require lots of wall space. In most buildings, adding this much baseboard is not a practical solution. Alternatives include using baseboard with higher heat output or using other types of heat emitters to achieve the necessary design load output.

Another option is to consider adding “high-output” finned-tube baseboard rather than standard baseboard. Figure 3 shows the heat available from one make and model of high-output baseboard (shown as the blue curve), and for comparison, standard residential baseboard (shown as the red curve).

The steps of the previous procedure can be modified to determine the amount of high-output finned-tube baseboard that is required to reduce the supply water temperature to the system under design load.

Steps 1-4: Same.

Step 5: Determine the output of high-output baseboard at the average circuit water temperature using Formula 3 (or manufacturer’s literature for a specific make and model).

Step 6: The required length of high-output baseboard to add to the system is found using Formula 3.

The required length of high-output baseboard

Where:

Lho = Length of high output finned-tube baseboard to be added (ft.)

design load = design heating load of building (Btu/h)

qL = Output of existing baseboard at the lower average water temperature (Btu/h/ft.)

Le = Total existing length of baseboard in system (ft.)

qho = Output of high output baseboard at the lower average water temperature (Btu/h/ft.)

Here’s another example: Assume a building has a calculated design load of 40,000 Btu/h, and its distribution system contains 120 ft. of standard residential finned-tube baseboard. The goal is to reduce the supply water temperature under design load to 120°. Additional high-output baseboard will be added to allow this lower water temperature operation. Assume the temperature drop of the distribution system at design load is 10° and this existing baseboard has the same output as in the previous example (146 Btu/h/ft., at average circuit water temperature of 115°). Determine the amount of high-output baseboard required based on the performance shown in Figure 3.

Determine the amount of high-output baseboard

Solution

Step 1: The design load has been calculated as 40,000 Btu/h;

Step 2: The total amount of finned-tube in the system is 120 feet.;

Step 3:  The new lower supply water temperature at design load will be 120°;

Step 4: The new lower average circuit water temperature will be 120 - 5 = 115°;

Step 5: The output of high-output finned-tube at an average water temperature of 115º F is determined from Figure 7 as 335 Btu/h/ft.; and

Step 6: The required length of high-output baseboard to add to the system is found using Formula 3.

The required length of high-output baseboard

Although this is a substantial reduction compared to the 154 ft. of additional standard baseboard required in the previous example, it still is a substantial length. The building must be carefully evaluated to see if this additional length of baseboard can be accommodated.

If the added length of high-output baseboard cannot be accommodated, another option is to raise the supply water temperature constraint from 120° to 130° under design load conditions. This would reduce the amount of added high-output baseboard to 40 feet.

 

Adding other heat emitters

If the amount of finned-tube baseboard that needs to be added is beyond what can be accommodated, there are several other added heat-emitter options, including panel radiators, fan-coil, or areas of radiant floor, radiant wall or radiant ceiling panels. In each case, the selection of these new heat emitters should be based on a selected supply water temperature at design load along with a “credit” for the existing heat emitters in the system operating at the lower supply water temperature.  The fundamental concept is given by Formula 4.

The fundamental concept

Where:

Qn = Required heat output of the new heat emitters at lower supply water temperature (Btu/h) design load = the design heating load of the building (Btu/h)

Qe = Heat output of existing heat emitters at the lower supply water temperature (Btu/h)

Once the value of Qn is determined, the designer can use tables or graphs from manufacturers to determine the heat output of specific heat emitters based on the average water temperature within them. Remember that the average water temperature will be 5° to 10° lower than the supply water temperature.

The goal is to select a grouping of new heat emitters with a total heat output that’s about equal to the value of Qn in Formula 4.

Let’s work through another example. Assume a building has a calculated design load of 40,000 Btu/h, and its distribution system contains 120 feet of standard residential finned-tube baseboard. The goal is to reduce the supply water temperature to 120° under design-load conditions. Panel radiators are available in a 24-inch by 72-inch size that can release 4,233 Btu/h when operated at an average water temperature of 115° in rooms with 70° interior temperature. How many of these radiator are necessary to meet the design load?

 

Solution

First, use Formula 4 to determine the output required of the new radiators.

Formula 4 to determine the output required of the new radiators

The number of radiators needed is then found as follows:

The number of radiators

The designer could either add six of these panel radiators or choose a slightly higher supply water temperature and use five radiators.

Another option is to use panel radiators of different sizes provided their total output at the lower supply water temperature could meet the value of Qn. In this example the six new radiators would be combined with the 120 feet of existing baseboard to provide the 40,000 Btu/h design load.

A similar calculation could be made for fan-coils, air handlers or other heat emitters.

In the case or radiant panels, the designer needs to determine the output of each square-foot of panel based on the lower average circuit temperature and the specific construction of the panel. The total required panel areas is found by dividing this number into the value of Qn.

Once the amount of additional heat emitter is determined, designers can turn their attention to how it should be piped into the distribution system. We’ll cover that next month in part two of this article.

 

To read the original article in pdf form, please see here.