Key advantages include reduced corrosion and
failure, and quicker dousing of a fire.
The design of an anti-freeze system depends on
whether or not it includes a backflow prevention device. If it doesn’t, the
arrangement of the supply piping and the valves would be as shown in the
Figure
1 cross-section. In this
detail, designated points #3 and #4 refer to a 3/4” gate valve and fill cup.
Point #6 refers to a supervised indicating valve, #8 to a 1/2” test valve, #5
denotes a 1” auxiliary drain valve, and #10 refers to a check valve with a
1/32” hole drilled in the clapper.
Often, an installer will simply shave off a corner of the clapper instead, to
allow for fluid expansion. NFPA 13
allows that the check valve be omitted entirely if all anti-freeze piping falls
below the elevation of the indicating valve (all antifreeze solutions are
heavier than water). The two test
valves (noted as #8) must be installed at least 48 inches apart. It should be noted that the gravity-fed fill
cup may be placed almost anywhere downstream of the check valve and is normally
installed at a high point of the piping.
Figure 2 is the NFPA 13-required supply arrangement for
anti-freeze systems containing a backflow preventer. In most jurisdictions, this device must be a reduced-pressure
type. This component will prohibit
water from flowing back into the water supply, but over-pressurization can
occur when pressure builds in the system as a result of thermal expansion
caused by temperature change.
When the fluid expands, the excess is discharged into the expansion
chamber. Within the vessel, the
gas-charged bladder compresses as the fluid enters the shell. All system components are thereby protected
because the chamber allows the trapped antifreeze to expand. Expansion tanks vary in size depending on
the volume of solution contained in the anti-freeze system.
All About Anti-Freeze
The two types of anti-freeze are propylene
glycol (PG) and glycerin. Section 7.6.2.4 of NFPA 13 states that “an antifreeze
solution shall be prepared with a freezing point below the expected minimum temperature
for the locality.” As an example, the freezing point for the Chicago area is
-22°F, which means that a glycerin solution used would contain 60% glycerin and
40% water. If propylene glycol is used, the correct mixture would be
50/50.
The solution must be thoroughly mixed with water before filling any system. An
over-concentration of antifreeze would be costly and may reverse the protection
desired, because beyond a certain point of over-concentration (around 75%) the anti-freeze will thicken
and cease to lower the freezing point of the solution. Installers should know (this is common
sense) not to mix any solutions in containers or drums that may be contaminated
with other substances.
It is imperative that the system be tagged with the manufacturer of the
anti-freeze, including all details and specifications of the fluid. When the
solution is field-tested (annually — as required by NFPA 25), testers can
determine the applicable concentration through the use of (hopefully) reliable
laboratory-grade hydrometers or refractometers of sufficient quality. For
hydrometers to produce accurate readings, the fluid temperature must be between
60°F and 68°F, or else a temperature correction shall be applied to the
reading.
After five years or so following installation, the solution may break down due
to small leaks, and concentrate will have to be added. After a stagnation
period that comprises 8-10 years without servicing, the system will require complete
solution replacement. If not properly maintained, the far ends of the piping
will no longer have the suitable mixture. When any section of the system
contains inadequate anti-freeze, freezing and breakage of sprinklers, pipe and
fittings will result. Not only will this comprise a filthy and expensive mess,
a frozen system cannot suppress a fire.
If the volume of an anti-freeze system exceeds 40 gallons, section 7.6.3.5
requires that an additional drain/test connection be added at the remote system
proximity — to provide another point for solution concentration level testing
(it is expected that the upcoming 2010 edition of NFPA 13 will alter this
section to include all anti-freeze systems regardless of
size).
When systems are larger than 150 gallons, an additional test valve must be
added for each 100-gallon increment. Survey reports have shown that
rubber-gasketed adjustable drop nipples installed in anti-freeze loops have a
tendency to leak.
In spite of the fact that anti-freeze
systems have been comprised of steel or copper piping for years, they are
generally not used with CPVC piping. When they are, only glycerin can be used
(per NFPA 13 and 25 requirements) as PG solutions will chemically attack CPVC
pipe joining compounds. With glycerin solutions, contamination may arise from
the use of recycled or off-grade glycerin.
Also, only thread paste sealant compatible with the particular CPVC
piping material is allowed.
Sealants and gaskets used in CPVC piped systems must also be checked for
compatibility, and most manufacturers provide chemical compatibility Web sites
such as
www.systemcompatible.com
to resolve any questions posed by the consulting engineer. Petroleum or
solvent-based lubricants or sealants must never be implemented. Mixing steel
and CPVC in the same system is generally a bad idea. For systems of steel or
CPVC, field survey reports have found that rubber-gasketed adjustable drop
nipples installed in anti-freeze loops are prone to leakage.
Cost Concerns
Engineers make things fit into the budget. Prior to the 2002 edition of NFPA 13, the
standard included the following advisory: “
because of the cost of
refilling the system or replenishing to compensate for small leaks, it is
advisable to use small dry valves where more than 40 gal are to be
supplied.” That section has disappeared from the code, meaning that
it’s now permissible to supply 50 sprinklers or more with an anti-freeze
system. But since solution costs exceed $20 per gallon, why would you do
that?
Over time, a dry-pipe system will require less maintenance, fewer service
calls, and is the safer system with regard to potable water. But if the system in
an unheated area exceeds 30 sprinklers, it may still be advisable to choose an
anti-freeze system for any of the following reasons:
- to avoid the purchase of an excessive number of dry
pendent sprinklers;
- to avoid the installation of a plethora of drum-drip assemblies — if
the new piping arrangement will contain numerous low
points;
- if the noise from an air compressor (i.e., behind a theatrical
stage) is not acceptable to the owner;
- there is virtually no floor space available for a dry
valve;
- plenum space is so tight that the potential dry pipe cannot be
properly pitched;
- or any additional electrical wiring has not been planned for or
desired.
One other advantage of the anti-freeze system is that the interior of the
piping will not scale as it would on a dry system. The reduction in corrosion,
then, will extend the life of the piping system. Also, the anti-freeze system
has a life safety advantage considering that, with dry systems, there is a
longer lag time (up to 60 seconds) for water to hit a spreading fire after a
sprinkler fuses.
In addition, there is an increased probability for system failure with the dry
system set-up. With anti-freeze systems, all that has to work is the sprinkler
itself. Barring any accidental valve closures, the system will work efficiently
to quickly extinguish any fire
By: mahdi
Posted: August 4, 2009 1:46 AM