This website requires certain cookies to work and uses other cookies to help you have the best experience. By visiting this website, certain cookies have already been set, which you may delete and block. By closing this message or continuing to use our site, you agree to the use of cookies. Visit our updated privacy and cookie policy to learn more.
This Website Uses Cookies
By closing this message or continuing to use our site, you agree to our cookie policy. Learn More
This website requires certain cookies to work and uses other cookies to help you have the best experience. By visiting this website, certain cookies have already been set, which you may delete and block. By closing this message or continuing to use our site, you agree to the use of cookies. Visit our updated privacy and cookie policy to learn more.
PM Engineer logo
search
cart
facebook twitter linkedin youtube
  • Sign In
  • Create Account
  • Sign Out
  • My Account
PM Engineer logo
  • Home
  • Magazine
    • Current Issue
    • Digital Edition
    • Archives
    • Radiant & Hydronics Report
    • Green Plumbing & Heating
    • Fire Protection & Design Special Section
    • NSF Design Special Section
    • Radiant Comfort Guide
    • PVF Outlook
    • Ad Index
  • Market Sectors
    • Green Plumbing
    • Green Mechanical Systems
    • Codes
    • Fire Protection
    • Radiant/Hydronics
    • Solar Thermal/Geothermal
    • Bath & Kitchen
    • Water Treatment
    • Technology
  • eNewsletter
    • Supply House Times e-news
    • pme eNewsletter Archives
    • Radiant & Hydronics eNews Archives
    • Bath & Kitchen Pro eNews Archives
    • Western Plumbing News Archives
    • Subscribe to Plumbing Group eNewsletters
  • Columnists
    • Julius Ballanco on Codes
    • Editor's Note
    • John Siegenthaler: Renewable Heating Design
    • Dan Holohan: Heating Help
    • Ray Wohlfarth: The Boiler Room
    • Jacqueline Wilmot: Fire Protection
    • Christoph Lohr: Professional Development Pipeline
    • Ethan Grossman: Water Cooler Conversations
    • Blog
  • Multimedia
    • PME AHR Expo 2019 Videos
    • pme Network Videos
    • eBook
    • Interactive Spotlights
    • Photo Gallery
    • Podcasts
    • Webinars
  • Products
  • More
    • History of Plumbing
    • Industry Calendar
    • Custom Content & Marketing Services
    • Classified Ads
    • Market Research
    • Bookstore
    • Continuing Education
  • Directories
    • B.I.G. Book
    • Rep Locator
  • Contact
    • Contact Us
    • Advertise
    • Editorial Submission Guidelines
Home » Boiler startup dangers
Ray Wohlfarth: The Boiler RoomRadiant/HydronicsColumnists

Boiler startup dangers

Leave no loose ends.

boiler dangers

A wiring terminal block for a commercial gas boiler. Photo credit: Ray Wohlfarth

boiler dangers

When the wiring connection is loose, the wire can be burned off, as shown here. Photo credit: Ray Wohlfarth

boiler dangers
boiler dangers
August 9, 2014
Ray Wohlfarth
KEYWORDS boiler / fire safety / safety
Reprints
No Comments

So, how many of these have you started over the years?” the contractor inquired.

He was asking about the boilers we sold him for this project. I mentally tried adding all the boilers I sold and replied with a sense of confidence, “I think between 300 to 400 over my career.” His question had kind of distracted me. I opened the burner control panel and gave a cursory glance at the wiring for the burner. It looked professionally installed as all the wires were bent and aligned symmetrically.

That was my first mistake. I assumed the burner was wired correctly and did not verify the wiring terminations. After all, when I asked the lead tech if he needed guidance on the wiring of the burners, he condescendingly told me, “Kid, I have been installing boilers for 20 years and know what I’m doing. I don’t need your help.” I hate when someone calls me Kid.

His response reminded me of a story a friend told me about hiring a seasoned salesman. This friend was called to sit in on a job interview for the new salesman and afterward was asked his opinion of one of the candidates.

“He has more than 20 years experience. I think I want to offer him the position,” the sales manager said excitedly to my friend.

“He doesn’t have 20 years experience. He has one year’s experience, 20 times. He does not seem to learn from his mistakes,” my friend responded to the sales manager.

While I am usually very methodical when doing a boiler startup, I overlooked the wiring. I progressed through the preliminary safety checks while the contractor foreman inspected the piping done by his crew. The manual main gas valve was closed but the pilot gas valve was open and I checked the flame safeguard for proper operation. After the safety controls were verified, I opened the manual main gas valve. The burner went through the pre-purge sequence which consists of operating the fan long enough to provide four air changes in the boiler.

After the pre-purge, which in this case was 90 seconds, the flame safeguard control energized the transformer. The 7,000 volts from the transformer created a spark to ignite the pilot flame. In that short minute and a half, the boiler, horizontal flue and chimney filled with natural gas. The ignition spark ignited the combustible mixture causing a loud booming explosion. My ears popped and rang for hours afterward.

Since I was bent down in front of the burner, the force of the blast went over me but I still felt the percussion in my chest and head. The force of the detonation was strong enough to twist the thick, welded-steel flue from the boilers to the chimney and also blew the flue completely apart from the adjacent water heater. The access door to the brick chimney, used for cleaning the smokestack, also was knocked off its hinges. I usually keep my hand on the shutoff switch for the first start of the burner in case something happens. I quickly turned the power off to the burner.

I had never needed to shut the burner off in my 30 years of boiler startups. In addition, both the foreman and I were covered with dirt, soot and frayed nerves. We looked like those old coal miner pictures from the 1800s. The explosion was so loud, it scared the people inside the building and they ran into the boiler room. I did not notice that the room was filled with dust until the people opened the boiler room door and the visibility was hazy.

 

Leave no loose ends

The cause of the explosion and one of my nine lives being expended was because their installer who had “more than 20 years experience” had inadvertently wired the main gas valves to the line voltage terminal. In other words, the gas valve was open any time the power was on to the burner. I was lucky as the main gas valve had been closed until right before the transformer sparked. After the flues for the boilers and water heaters were replaced and we verified that the chimney, boilers and water heater were still operable and safe, I changed the wiring connections to the correct terminals and verified that all the other wires were properly terminated. I now check every wire connection for the boiler and burner to assure they are on the correct terminal.

Speaking about wiring terminal connections, a loose wire can drive a service technician crazy. When servicing the burner, always verify the screws holding the wires in place are snug. It is amazing how many burners are shipped with loose wiring connections on the wiring terminal. I make sure I check the tightness of each wire when performing regular service on the boiler as well. The burner blower on a power burner typically operates at 1,700 revolutions per minute or higher. This causes vibration which loosens the wiring connections.

I have been called the Obsessive Compulsive Dad by my kids because I have been known to straighten crooked pictures while in public but I am not nearly as bad as the first journeyman I worked for in the trade. When he worked on a piece of equipment, he would align all the screw slots to the same orientation. He would say, the alignment shows that the installer was professional. As I got my confidence, I used to turn one screw perpendicular to the others, just to tease him.

On another project, I found that the burner had no power. The cause was a loose connection on the main power terminal and the wire melted the connection, which could have led to a fire. The picture to the left shows what happens to a terminal when the wiring connection is loose.

When starting or servicing a boiler, always check the wiring connections for snugness and proper termination.

 


HELPFUL LINKS:

  • Contact pme
  • Follow pme on Twitter!
  • Find pme on Facebook!
  • Join pme on LinkedIn!
  •  pme is on Google+ 

Subscribe to PM Engineer

Recent Articles by Ray Wohlfarth

Ray Wohlfarth: Troubleshooting hydronics

Ray Wohlfarth: The case for 2 psig

Ray Wohlfarth: Saying goodbye to industry legend, Bill Vallett, Sr.

Ray Wohlfarth: Understanding boiler controls

Why is the relief valve leaking?

Raynew_200

Ray Wohlfarth is the author of “Lessons Learned in a Boiler Room: A common-sense approach to servicing and installing commercial boilers.” In his spare time, he is president of Fire & Ice in Pittsburgh. Ray writes a monthly newsletter on commercial boilers. He can be reached at 412/343-4110 or ray@fireiceheat.com.

Related Articles

Are boilers dangerous?

Carbon monoxide dangers

Concussion dangers in a boiler room

You must login or register in order to post a comment.

Report Abusive Comment

Subscribe For Free!
  • Print & Digital Edition Subscriptions
  • eNewsletters
  • Online Registration
  • Subscription Customer Service

More Videos

Popular Stories

John Siegenthaler: Renewable Heating Design

John Siegenthaler: Pellet-fired boilers need thermal storage

Chis Wysoczanski, P.E.

2019 pme Mechanical Engineer of the Year: Fitzemeyer & Tocci's Chris Wysoczanski, P.E.

Julius Ballanco

Julius Ballanco: Not much changed at IAPMO

Ethan Grossman

Ethan Grossman: Getting dirty in engineering

Christoph Lohr

Christoph Lohr: Looking at the importance of personality metrics

Mechanical Engineer of the Year 2017 360

Events

December 30, 2030

Webinar Sponsorship Information

For webinar sponsorship information, visit www.bnpevents.com/webinars or email webinars@bnpmedia.com.

View All Submit An Event

Products

2020 National Plumbing & HVAC Estimator

2020 National Plumbing & HVAC Estimator

See More Products

PME-PlumberEngineer2017_360.png


PME Rep Locator

PM Engineer Magazine

PME November 2019

2019 November

Check out the November 2019 edition of PME: PME's Mechanical Contractor of the Year, drainage trends, pellet-fired boilers, flue gas venting, and much more!
View More Create Account
  • Resources
    • List Rental
    • Reprints
    • eNewsletters
    • Contact Us
    • Privacy Policy
    • Editorial Submissions
  • Want More?
    • Subscribe
    • Industry Links
    • Connect
    • Survey And Sample
  • Plumbing Group
    • Plumbing & Mechanical
    • Supply House Times
  • Advertise
    • Advertise
    • Plan For 2020!

Copyright ©2019. All Rights Reserved BNP Media.

Design, CMS, Hosting & Web Development :: ePublishing