Active Pressure Control Devices and Vent Systems for Building Drainage and Vent Systems
by Jack Beuschel
April 13, 2007
When
used together, air admittance valves and the positive air pressure attenuator
device can effectively balance safety, efficiency and functionality.
Note:
This article is mainly comprised of excerpts from a recent study prepared by
Professor John Swaffield and Dr. Michael Gormley of Heriot-Watt University in
Scotland titled Building Drainage Waste and Vent Systems: Options for Efficient
Pressure Control. Copies of this study can be obtained by contacting Studor,
Inc. at (800) 447-4721.
|
|
| Figure1. Fully vented system with open top and parallel vent pipe. |
|
There
are few real mysteries remaining about the mechanisms at play in building
drainage and vent systems. This has been well understood from the beginning of
modern sanitary engineering, which dates back to the end of the 19th century.
The description of building drainage and vent system operation is best
understood in the context of engineering science in general and fluid
mechanics.
At the center of the drainage system’s integrity is the water trap seal, which
stops sewer gas from entering a habitable space from the sewer. The water trap
seal is usually 2 inches in depth depending on the fixture it is
protecting.
It comes as a surprise to many that the flow of air is as important, if not
more important, to the safe operation of the drainage system as the flow of
water. This air flow is ‘induced’ or ‘entrained’ by the flow of water. The
unsteady nature of the water flows causes pressure fluctuations (known as
pressure transients), which can compromise water trap seals and provide a path
for sewer gases to enter the habitable space.
Pressure Transients
|
|
| Figure 2. Two-story house with AAVs on branches and AAV termination at the top of the stack. |
|
Transients
can be dealt with by a combination of careful design and the introduction of
pressure control devices as close to the area of concern as possible. Long vent
pipes can be an inefficient way of providing relief due to friction in the
pipe. Distributing air supply inlets using air admittance valves (AAVs) around
a building provides an efficient means of venting by allowing air to enter the
system, and they also reduce the risk of positive transient generation. AAVs do
not cause positive pressure transients, they merely respond to them by closing,
and hence, reflect a reduced amplitude wave.
The introduction of a positive air pressure transient alleviation device known
as the Positive Air Pressure Attenuator (PAPA) provides a means to ‘blow off’
pressure surges as close as possible to their source, thereby protecting water
traps. Attenuation of up to 90% of the incident wave can be achieved, thus
protecting the entire system. It should be noted that there is little that can
be done for a system experiencing a total blockage, generating excessive static
positive pressures in the drainage system. In such circumstances, the lowest water
trap seal will ‘blow’—providing relief for the whole system. This will occur
regardless of the method of venting employed.
In validated test simulations, AAVs have been shown to provide at least as good
protection for water trap seals as a system completely vented with piping to
the outdoors, and in tall buildings in some circumstances, AAVs provide even
better protection. The fully engineered designed active control system
utilizing AAVs for negative pressure relief and PAPAs for positive transient
relief is shown to be an effective method for balancing the need for safety and
efficiency while maintaining functionality invisible to the user.
A negative pressure transient communicates a need for more air and represents a
suction force, while a positive pressure transient communicates the need to
reduce the air flowing and represents a pushing force. A negative transient can
be caused by air leaving the system (hence the need for more air), and a
positive transient can be caused by the air reaching a closed end (stopping the
air where there is no escape route).
A negative transient will attempt to suck water out of a water trap seal. The
pressure differential may not be sufficient to completely evacuate the water
the first time, but the effect can be cumulative. Positive air pressure
transients cause air to be forced through the water seal from the sewer side to
the habitable space inside.
The need to communicate an increase or decrease in the air-flow and the finite
time that this takes is central to the requirements of providing a safely
engineered drainage system. The absolute key to maintaining a state of
equilibrium in a drainage system is to provide pressure relief as close to
where it will occur as possible. If negative pressure transients are a call for
more air, then positive pressure transients are a call to stop sending
air.
Modeling Flows in Drainage Networks
|
|
| Figure 3. Comparison of water retained in the ground floor trap (shaded on schematic of Figure 4.) |
|
Research
and analysis of real building drainage systems is complicated by the difficulty
in obtaining data from ‘live’ buildings. Most areas of engineering employ some
form of modeling technique in research and development in their ‘look and see’
approach to development. In DWV research, there are few models capable of
dealing with the complex time-dependent transient flows.
The computer model AIRNET, developed by Professor John Swaffield, Heriot-Watt
University (Scotland), is capable of such a complex task. At the heart of the
AIRNET model is the mathematical technique known as the method of
characteristics. The technique allows the propagation of waves to be predicted
along the length of a pipe at different time steps. This is a very powerful and
unique way to ‘look and see’ what is actually going on inside a building
drainage system. The simulations (discussed on the following page) in a
specific study were carried out using AIRNET.
Two-Story Building Simulation
|
|
| Figure 4. Three installation types in 10-story building simulation. |
|
A
two-story building drainage system can operate sufficiently well with minimal
additional ventilation as long as it is designed and installed properly. This
is borne out by reference to the installation shown in Figure 1 and Figure 2. The building represents a fairly common house with a number of
bathrooms and a group branch in a kitchen/laundry area. The simulation was run
in two different scenarios:
1. System with an open pipe vent
2. System with AAVs
A discharge flow rate was simulated from the top floor consisting of a combined
flow from a WC and a bath. This discharge was simulated from the upper floor
and the effect on the water trap indicated by shading was recorded from the
output data. It can be seen from the bar graph shown in Figure 3 that little
water has been lost as a result of the operation of system devices in either
scenario.
10-Story Building Simulation
|
|
| Figure 5. Comparison of water retained in the lowest water trap (shaded on schematic in Figure 4.) Conditions based on negative transient. |
|
The
10-story building scenario is shown in the variations of Figure 4.
There are basically three installation types being simulated here. The first is
a fully vented system (see Figure 4a). The second is a one-pipe system with
distributed venting and an AAV on the top of the stack (see Figure 4b). This
system also includes a relief vent. The third (Figure 4c) is the one-pipe
system with distributed AAVs and PAPAs subjected to a positive air pressure
transient simulated to replicate the occurrence of a surcharge in the sewer. In
each of the scenarios a representative water trap is shown on three floors in
the building.
The flow rate used in this simulation represents a maximum for the 4"
vertical stack in question (80 gpm). This flow rate is unlikely to be observed
in practice, as the simultaneous discharges required are a probabilistic
impossibility (Hunter 1940). The flow rate is therefore indicative of a ‘worst
case scenario’ in order to push the drainage vent system to its limits, and
therefore show comparisons between the options investigated. The discharges
making up the flow rate are distributed evenly along the stack to simulate a
number of simultaneous discharges (approximately 16 gpm from five different
floors).
The bar graph shown in Figure 5 illustrates the water depth retained in the
shaded water trap in Figure 4 following this event. It can be seen that under
these conditions, the system with AAVs installed (Figure 4b) has retained more
water than the open pipe system (Figure 4a). Why is this? The main reason is
that the flow in the vertical stack induces a negative pressure transient as it
calls for more air. This negative transient propagates to all parts of the
system “looking for air.” The negative transient represents a suction force
that will try to draw water out of the trap seal. If the negative transient is
too great, it will suck water out of the trap. To stop this happening, air must
be provided from somewhere else.
Two different methods are shown in Figure 4a and Figure 4b. In Figure 4a, the
air must travel from the top of the stack, approximately 100 feet away (but
only after the negative transient has propagated to the top of the stack first,
so the round trip is approximately 200 feet). Alternatively, air can be
provided locally by the provision of an AAV (Figure 4b). In this case the round
trip is only a matter of 10 feet. This means that the air can be provided
quicker than with the fully vented system.
Figure 6 shows the trap retention on
the same trap as the result of a positive pressure transient in the system. The
positive transient was generated by simulating a surcharge in the sewer,
causing the airflow through the stack to be stopped. Again, there are three
methods of dealing with this scenario: the fully vented system shown in Figure
4a and the ‘active control’ option utilizing AAVs and PAPAs as shown in Figures
4b and 4c. The bar graph of trap retention clearly shows that the active
control system shown in Figure 4c provides the best protection against this
sort of event, and that the AAV system with a relief vent shown in Figure 4b
provides better protection than the fully vented system in Figure 4a.
The reasons for active control being better are two-fold: first, the
distribution of the air inlets reduces the maximum positive pressure possible;
and second, the PAPA presents a volume that can consume the positive pressure
wave, attenuate it and destroy it, rendering it harmless. This is borne out by
the amount of water displaced by the positive pressure
wave.
Conclusion
|
|
| Figure 6. Comparison of water retained in the ground floor trap indicated (shaded on shematic in Figure 4). Condition based on positive transient. |
|
Air
admittance valves (AAVs) have been installed worldwide since the early 1970s
and in North America since 1989. Millions of valves have been installed; they
have been field-tested and are operating successfully. The Positive Air
Pressure Attenuator (PAPA), which was invented by Professor John Swaffield and
Dr. David Campbell of Heriot-Watt University, Scotland, was introduced in North
America in 2004.
Since their introduction, five major high-rise buildings (with AAVs and PAPAs
installed) have been completed in the U.S., and there are six more projects
under construction in which AAVs and PAPAs have been specified. In addition to
U.S. installations, AAVs and PAPA systems are being installed on a regular
basis worldwide. Design professionals have realized that these “active pressure
control devices” are a viable option to open pipe venting and Sovent® systems.
|