by Christian Dubay, P.E.
January 11, 2010
Major technical changes are contained within the 2007 edition of NFPA 13 relating to seismic protection of automatic sprinkler systems.
Editor’s Notes: This article originally appeared in the Jan. 2007 issue of Sprinkler Age. Parts 1 and 2 of this series originally appeared in the October and December 2006 issues of Sprinkler Age. Reprints of Parts 1 and 2 of this series appeared in the January and July 2009 issues of pme.
This is the final part in this series, which addresses the major technical changes that are contained within the 2007 edition of NFPA 13 relating to seismic protection of automatic sprinkler systems. This series does not cover each and every change or review the existing requirements that have been contained in previous editions of NFPA 13. The 2007 edition made specific seismic changes in nine specific areas. Each of these areas will be discussed in detail with the final text of NFPA 13 included in quotation marks.
All figures, table and except reproduced with permission from NFPA 13-2007, Installation of Sprinker Systems, copyright © 2006 NFPA. This excerpt does not represent the complete and official position of the NFPA on the referenced subject, which is represented only by the standard in its entirety.
The final area where significant changes were made was in the area of restraint of branch lines. In previous editions of NFPA 13, restraint was only required for branch lines where impact or damage was possible due to movement of the system piping during the seismic event. However, in updating the requirements of NFPA 13 to ensure compliance with ASCE 7, it was determined that restraint is required for all branch lines.
Two new figures [see Figures A.9.3.6.1(5)(a) and (b)Hangers Used in Combination] were added to illustrate another acceptable method of branch line restraint. Section 9.3.6.1(5) permits the use of two generic listed hangers to be installed as required by 9.3.6.1(5), where combined the hangers restrain the vertical and horizontal movement.
“(5)*A hanger not less than 45 degrees from vertical installed within 6 in. (152 mm) of the vertical hanger arranged for restraint against upward movement, provided it is utilized such that l/r does not exceed 300, where the rod shall extend to the pipe or have a surge clip installed”
Section 9.3.6.4 provides the maximum distance between branch line restraints and is based upon the Cp for the system, which was previously discussed. Specifically, Table 9.3.6.4 relates the Cp to the maximum spacing of restraints.
“9.3.6.5 Where the branch lines are supported by rods less than 6 in. (152 mm) long measured between the top of the pipe and the point of attachment to the building structure, the requirements of 9.3.6.1 through 9.3.6.4 shall not apply and additional restraint shall not be required for the branch lines.”
Christian Dubay, P.E.
Christian Dubay, P.E., is vice president and chief engineer at the National Fire Protection Association and the editor of the Automatic Sprinkler Systems Handbook. Dubay holds a bachelor of science degree in fire protection engineering from the University of Maryland. He is a registered professional engineer in the State of Connecticut and is a member of the Society of Fire Protection Engineers.
Did you enjoy this article? Click here to subscribe to the magazine.
Virtual encyclopedia on modern hydronic systems.
CONNECT WITH PM ENGINEER: