Harvesting Btu
by John Siegenthaler , P.E.
December 1, 2011
How to extract more heat from a storage tank.
Nearly all solar thermal combisystems have a large, insulated tank that
stores heat gathered from the collectors. The water temperature in this tank
varies considerably from hour to hour depending on solar input (or lack
thereof), as well as heat extraction by the load(s).
When there is a demand for space heating, the control subsystem must decide if
the tank is warm enough to supply the load. If not, it must enable operation of
the auxiliary heat source. When a low-temperature hydronic distribution system
is used, that auxiliary heat source is often a modulating/condensing boiler.
Figure 1 depicts a typical space-heating system in which a closed-loop
collector array operating with antifreeze and a heat exchanger supplies a large
(pressurized) thermal storage tank. The piping on the right side of this tank
allows either that tank or the auxiliary mod/con boiler to supply the
low-temperature radiant-panel distribution system. For the time being, this
schematic has no subsystem for domestic water heating. We’ll add that shortly.
Upon a demand for space heating from any heating zone, an outdoor reset
controller is powered on to measure the temperature at the top of the storage
tank, and compare it to a calculated “target” supply water temperature. If the
tank is deemed sufficiently warm to supply the zones, circulator (P2) is turned
on to deliver heated water to the closely spaced tees that hydraulically
separate the distribution system from the heat sources. If the storage temperature
is too low to supply the load, the auxiliary boiler is turned on along with
circulator (P1). Again, heated water is delivered to the closely spaced tees
and carried onward into the distribution system by the variable-speed,
pressure-regulated circulator.
Adding DHW
Figure 2 shows one way to extend the system shown in Figure 1
to leverage the thermal mass of the storage tank for preheating (or fully heating)
domestic water on an “instantaneous” basis.
A flow switch detects whenever domestic water is required at a flow rate of 0.5
gpm or above. Under this condition, it turns on a small circulator that moves
heated water from the storage tank through the primary side of a
stainless-steel, brazed-plate heat exchanger. Cold water is instantaneously preheated
(or fully heated depending on the tank temperature) as it passes through the
other side of the heat exchanger.
An electric tankless water heater provides any necessary boost in domestic hot
water delivery temperature. An anti-scald-rated thermostatic mixing valve
protects against high domestic water temperatures when the storage tank is at
an elevated temperature. For the fastest possible response, the piping between
the storage tank and heat exchanger should be short and fully insulated. This
configuration allows for preheating domestic water whenever the storage tank is
above the temperature of the entering cold domestic water.
Extracting More Heat
One limitation of this basic control logic is there is no operating mode
where
both
the storage tank and auxiliary boiler can supply heat to the load.
Consider the situation where the temperature at the top of the storage tank is
slightly lower than the lower limit established by the outdoor reset controller,
but
still warmer than the return temperature of the distribution system. Under these conditions, the tank can
still contribute some heat to the space-heating load. The remaining heat would
be supplied by the auxiliary boiler.
The addition of a second differential temperature controller (abbreviated as ∆T
controller), like that used to control the solar subsystem, allows the storage
tank to be used at a lower temperature.
Figure 3 shows where
the sensors for this ∆T controller would be located.
Figure 4
shows a ladder diagram containing the hard-wired logic for the overall
system.
If the outdoor reset controller determines the tank is too cool to supply the
load, its normally open contact closes to power up the ∆T controller as well as
a relay that enables the boiler to operate and places control of circulator
(P2) solely at the discretion of the ∆T controller.
The ∆T controller measures the temperature difference between water at the top
of the storage tank and that returning from the distribution system. If the top
of tank is at least 2º F above the return temperature, the normally open
contact in the ∆T controller closes to keep circulator (P2)
operating.
The boiler and circulator (P1) also are operating at this time. The boiler is
monitoring the temperature downstream of the closely spaced tees. Ideally, it
modulates to add just enough heat to maintain this temperature close to the
target temperature required by the distribution system, based on the settings
of its internal reset controller.
The mixing valve, operating under its own outdoor reset controller and
with the same settings as the boiler reset controller, should be at or very
close to its fully open position.
If the temperature difference between the top of the storage tank and the
return side of the distribution system drops to less than 1° F, there is very
little heat being extracted from the tank. Under this condition, the ∆T
controller turns off circulator (P2) to prevent heat supplied by the auxiliary
boiler from being added to the storage tank. The auxiliary boiler and
circulator (P1) remain on to supply the space-heating load as
required.
When the storage tank temperature again rises to where the temperature
differential between the top of the tank and the return side of the
distribution system reaches 2° F or more, the circulator (P2) is turned back on
to again extract available heat from the tank.
This strategy makes sense when a large storage tank is used in the system. I
suggest it only be used when the storage tank contains at least 500 gallons.
The ability to lower 500 gallons of water by an additional 10º F implies a
release of almost 42,000 additional Btu from the tank. Smaller tanks would
contribute proportionally smaller amounts of heat, and thus provide less
justification for the additional controls.
If you implement this strategy, be sure the temperature sensors for the ∆T
controller are mounted in identical or nearly identical manners. Ideally, both
sensors would be mounted in identical sensor wells, immersed in the system
water, and with ample coatings of thermal grease. If mounted to the surface of
copper tubing, be sure the sensor surface makes good contact, is well-secured
and is fully wrapped with insulation.
Remember, you’re asking the ∆T controller to detect differences in temperatures
as low as 1° F. That’s about 1/3 the temperature difference you can detect with
your own fingers.
John Siegenthaler , P.E.
john@hydronicpros.com
Links
Contact PM Engineer >> Send
pme your feedback by visiting our Contact Us page. View staff e-mail and mailing addresses, or send us a Letter To The Editor.
Follow pme on Twitter! >> Follow
pme’s news
feed daily on Twitter where we're tweeting industry-specific links and
information @PMEngineer.
Did you enjoy this article? Click
here to subscribe to the magazine.
CONNECT WITH PM ENGINEER: