Well-Grounded Solar
by John Siegenthaler , P.E.
February 1, 2011
A versatile way to integrate solar thermal and geothermal heat pumps.
Two thermally based renewable energy technologies that grab many
headlines these days are solar water heating and geothermal heat pumps. Both now
enjoy the “favored status” of a 30% income tax credit from Uncle Sam, as well
as numerous other rebates and credits at the state level.
Solar thermal systems and geothermal heat pump systems are both ways of
capturing solar energy. The solar thermal system does it in real time, whereas
the geothermal heat pump system, operating from a horizontal earth loop,
extracts solar heat driven into the soil several months earlier. This time
shift between when the energy is available and when it’s needed allows
combinations of solar thermal hardware and geothermal heat pumps to be complementary.
Take a look at the system schematic in Figure 1. It combines
both solar thermal and geothermal heat pump subsystems into an overall system
for space heating, space cooling and domestic water heating.
Heating Mode
The primary heat source for space heating is the water-to-water
geothermal heat pump. During the heating season it extracts low temperature
heat from the earth loop, converts it to higher temperature heat and parks that
heat in a well-insulated buffer tank.
When the heat pump is gathering heat from a horizontal earth loop, the fluid in
the earth loop is at a relatively low temperature, especially during mid to
late winter. In a Northern climate, this fluid may even be, at times, less than
32º F. In such systems the earth loop fluid is typically a 15% to 20% solution
of propylene glycol or other antifreeze.
A low-temperature distribution system delivers that heat when and where it’s
needed. A variable-speed, pressure-regulated circulator operates in response to
the differential pressure across the headers. When a zone valve opens, the
differential pressure across the headers attempts to decrease. The circulator senses
this electronically and immediately increases its speed to restore the original
(design) differential pressure.
The heat pump responds only to the temperature of the buffer tank, as monitored
by an outdoor reset controller. The “responsibility” of the heat pump, based on
this control scenario, is to keep the buffer tank temperature within a certain
range of a target temperature whenever space heating may be required. The
latter is calculated based on the settings of the reset controller and the
current outdoor temperature. This approach minimizes the temperature of the
buffer tank based on the prevailing conditions. In doing so, it improves both
the heating capacity and coefficient of performance of the heat pump.
Figure
2 shows an example of how the reset line of such controller could be
set for a low-temperature distribution system.
Cooling Mode
A similar operating mode is used for chilled water cooling. The heat
pump chills the buffer tank and dissipates the absorbed heat to the earth loop.
Chilled water flow is controlled by a second variable-speed, pressure-regulated
circulator in response to zone valves on each chilled water air handler. The
temperature of the buffer tank is now likely to be controlled by a setpoint
device that keeps the water in the range of 45º F to 60º F whenever the cooling
mode is active.
This configuration works well provided
the building does not require heating and cooling within a short time of each
other. It’s obviously not very efficient to heat the buffer tank to supply heat
in the morning and then cool it down to supply cooling that afternoon.
There are climates where heating is required in the morning, followed by a need
for cooling in the afternoon. In such cases, one operating mode has to take
precedence during swing seasons, or unusual weather conditions, until the
system settles into a stable mode for the duration of the season. Another more
costly and complex solution is to design the system with two buffer tanks — one
for heated water and the other for chilled water.
Solar Assist
The solar subsystem shown in Figure 1 allows for two operating
modes:
B>a. The solar heat collected is delivered to the DHW
storage tank through the tank’s internal coiled heat exchanger.
b. The solar heat is delivered to the earth loop through the
brazed-plate heat exchanger.
If the sun is out, and the domestic water temperature is lower than some limit
(say 140º F), the diverter valve routes the fluid leaving the collector through
the tank’s internal coiled heat exchanger.
If the tank reaches the upper limit, and the sun is still shining, the diverter
valve would reroute flow from the collector array to a brazed-plate heat exchanger
in the earth loop. Connecting the collectors to the earth loop forces them to
operate at a relatively low temperature, perhaps just a few degrees above that
of the earth loop fluid. Under this operating mode, the collector array is
partially unloading the earth loop.
Over time this will keep the soil around the earth loop slightly warmer than it
would otherwise be without the solar assist. This operating mode is
particularly appealing in late winter and early spring when the fluid
temperature supplied by horizontal earth loops is bottoming out at the same
time solar gains are getting stronger.
In past columns I’ve tried to emphasize the point that the lower the operating
temperature of the collectors, the higher their thermal efficiency. For example,
a typical flat- plate collector operating with an entering fluid temperature of
40º F, at a time when the solar radiation intensity is 250 Btu/hr/ft2,
and an outside temperature of 30º F, has a thermal efficiency of about 67%. If
the inlet temperature to this collector was raised to 120º F under the same ambient
conditions, its thermal efficiency would be only about 37%. This implies that
the collector operating at the lower temperature is gathering about 80% more
heat than the collector operating at the elevated
temperature.
Based on this, some of you may be thinking, “If the efficiency is so much
higher, why not just connect the collector array to the earth loop and forget
about operating it at a higher temperature for domestic hot water?” The answer
is based on two considerations: First, if “auxiliary” water heating is provided
by an electric element (or electric tankless heater), the cost of that heat may
be three or four times greater than the cost of heat produced by the heat pump
(assuming the latter has an average COP of 3 or 4).
Thus, displacing heat produced by the electric heating element will always be
more cost-effective and should be the “priority” mode. Secondly, if the
collector array is only connected to the earth loop, it serves no purpose
during warmer weather when the heat pump is operating in cooling mode. In this
mode the earth loop should remain as cool as possible. During this time there’s
plenty of solar energy available to heat water, but no way to collect
it.
When the heat pump is operating in cooling mode, the diverter valve directs the
hot antifreeze solution returning from the collector array through the heat
exchanger in the solar storage tank. In this mode the solar subsystem is
effectively isolated from the heat pump system.
Other Possibilities
The foremost “Achilles’ heel” of closed-loop, antifreeze-based solar
thermal systems is what to do with excess solar heat in summer. Simply turning
off the collector circulator if the storage tank reaches a high limit can cause
rapid degradation of glycol-based antifreeze fluids within the collector. It
can also cause steam flash in the collector array and the opening of the
collector circuit pressure relief valve.
The system shown in Figure 1 allows the option of dumping excess solar heat
gain to the earth loop. The diverter valve directs fluid from the collector
array through the brazed-plate heat exchanger in the earth loop while the earth
loop circulator operates.
In heating-only systems, or systems with minimal cooling load, this heat dump
mode is easy to implement. The possibility of “overheating” the earth loop due
to occasional heat dumping is certainly less in Northern climates where earth
loop temperatures, even during late summer, are in the range of 65º F to 80º F.
However, this mode may or may not be viable in locations with long/hot summers,
and thus significant cooling loads. I see it as possible provided the temperature
of the earth loop fluid entering the heat pump doesn’t rise above a point where
heat pump cooling performance is significantly reduced. This could be detected
by a setpoint controller with the subsequent action of invoking another means
of heat dumping. This also assumes heat dumping is an occasional occurrence,
rather than something that occurs every sunny summer day.
More To Come
It’s possible to combine solar subsystems and geothermal heat pumps in
other ways. One uses the solar array to
add heat to the same storage tank that is otherwise heated by the ground-source
heat pump. A coil heat exchanger suspended in the upper portion of this tank,
or a brazed-plate heat exchanger outside the tank serves to preheat domestic
water. I had such a system in my own home for several years and it worked well.
I would likely still have it had we not added building space that required more
capacity than the heat pump could deliver.
I expect more research will be undertaken on how to best combine arrays of
solar collectors with geothermal heat pumps. The “optimal” configuration must
address the relative size and timing of the space heating, space cooling and
DHW loads. Look for this combination of subsystems to remain a popular topic in
the future.
John Siegenthaler , P.E.
john@hydronicpros.com
Links
2009 Hydronics Know How II CD >>
Great Gift Idea!
This digital collection is a virtual encyclopedia on modern hydronic systems.
The Hydronics Know How II CD contains ALL the columns and articles John Siegenthaler has written for Plumbing & Mechanical and PM Engineer. That’s over 200 articles and columns covering everything from heat loss to hydraulic separation. Retail Price: $99.00
Visit AECStore.com for a complete description. To order by phone, call Stephanie at 248/244-1275.
Contact PM Engineer >> Send
pme your feedback by visiting our Contact Us page. View staff e-mail and mailing addresses, or send us a Letter To The Editor.
Follow pme on Twitter! >> Follow
pme’s news
feed daily on Twitter where we're tweeting industry-specific links and
information @PMEngineer.
Did you enjoy this article? Click
here to subscribe to the magazine.
CONNECT WITH PM ENGINEER: