by John Siegenthaler , P.E.
October 1, 2010
A by-the-numbers approach for determining the air volume required at the top of a drainback storage tank.
One of the simplest and most reliable configurations for a solar thermal
combisystem makes use of drainback freeze protection. The concept is really
simple: Drain the water out of the collectors and exposed piping whenever the
collector circulator is not operating. This includes nighttime, low sun
conditions as well as during a power failure or if the maximum-allowed tank
temperature condition occurs during sunny conditions. The latter two conditions
allow the collectors to “dry stagnate” without concern over degradation of the
antifreeze fluids used in other types of systems.
Although there are several ways to configure components for drainback freeze
protection, my favorite approach uses the top of the storage tank to hold the
drainback volume and accommodate the expansion of water within the system when
it is heated. This eliminates the need for a conventional expansion tank. An
example of this configuration is shown in Figure 1.
This article discusses the specifics of sizing the air space at the top of the
tank. The formulas given are based on vertically oriented cylindrical pressure
vessels.
To determine the required space at the top of the tank, one must establish criteria for the changes in temperature, pressure and volume of the captive air that will occur between two limiting conditions.
The minimum height (h) of the cylindrical air space at the top of a tank with flat ends can be calculated using Formulas 1, 2 and 3.
Formula 2
Formula 3
Where:
In other words, this formula states that the absolute pressure of a
quantity of air multiplied by its volume and divided by its absolute
temperature remains a constant.
So how did the relatively simple Formula 4 spawn off the three more complex
formulas? It comes from defining specific constraints for the tank (in this
case a vertical cylinder with flat ends) along with the initial and final
conditions for the captive air volume in the system, and making sure all
pressures and temperatures are expressed as absolute temperatures and absolute
pressures (e.g., absolute temperature = ºF + 460; absolute pressure = gauge
pressure + 14.7).
Here’s an example of how to use these formulas, assuming you are sizing up a tank for a drainback system. The tank you’ve selected has flat ends, a volume of 250 gallons and an internal diameter of 30 inches. The system is filled with water at 60º F, and the air space at the top is left at atmospheric pressure (e.g., gauge pressure = 0). The distribution system (exclusive of the storage tank and collector subsystem) contains 50 gallons of water. The maximum temperature condition assumes that all water and captive air in the system reaches 180º F. The latter is a conservative assumption because it is unlikely the entire distribution system will reach this high temperature. A 30 psi-rated pressure relief valve is installed at the top of the tank. What is the minimum vertical dimension of the air space at the top of the tank to accommodate expansion?
Before using Formula 1, we need to know both S and R. To find R we need the density of water at 60º F and 180º F. These values can be found in several references, or calculated using Formula 5.
Where:
The values of R and S, along with the other given data, can now be used in Formula 1.
This means just under 2 inches of vertical space at the top of the storage tank, in combination with the volume of air in the collectors and collector piping (above the static water level), is sufficient to keep the pressure from exceeding the pressure-relief valve rating when all water and air in the system is at a temperature of 180º F.
Where:
v = volume of the expansion space within the tank (gallons)
d = tank diameter (inches)
h = minimum height of cylindrical air space (inches)
If you’re familiar with sizing nondiaphragm-type expansion tanks, this volume
probably seems a bit low for a system with almost 300 gallons of water being
heated from 60° F to 180º F. However, keep in mind that the volume of the
collectors and the piping to and from them is also filled with air and thus
acting as an expansion space. If the collector circulator is running, this air
volume is just moved from the collector into the storage tank. For the previous
example this adds another 10 gallons to the system’s air volume, making the
total expansion air volume around 15.5 gallons.
Also keep in mind that (h) is the minimum air space height required. You can always opt to be a bit more conservative and include more air space or change the limiting constraints. For example, I often suggest subtracting 5 psi from the rated pressure of the relief valve as the maximum pressure the valve should reach with assurance it will not “dribble.”
You can calculate the drop in water level (∆H) within the tank when the collector circulator is operating using Formula 6.
Where:
Also, be sure the piping connection leading to the distribution system is at least a couple of inches below the water level in the tank when the collector circulator is operating.
Here’s a final example to show how things can change with different tank geometry and relief valve settings. Assume the tank is only 22 inches in diameter but still has a total volume of 250 gallons. The array collector piping above the static water level has a total volume of 5 gallons. As in the previous example, the distribution system has a volume of 50 gallons. Assume the pressure-relief valve is rated at 15 psi, and that the same minimum and maximum water temperatures (60° F and 180º F) remain in effect.
The value of R remains the same since the limiting temperature didn’t change:
The minimum air space height can now be calculated using Formula 1:
This is a substantial change in the minimum air space height. It is due
to a decrease in tank diameter, a decrease in the pressure relief valve setting
and a smaller collector volume.
The combined volume of the air space in the tank and the collector array plus
collector piping is now about 22.7 gallons.
Use the formulas and data given in this article, perhaps as a spreadsheet, to
determine the minimum required height of the air space at the top of the drainback
tank. Then, add at least an inch or two to the required height as a further
safety margin. Although the mathematics may look a bit messy, the underlying
physics of drainback systems are simple, reliable and efficient.
John Siegenthaler , P.E.
john@hydronicpros.com

Did you enjoy this article? Click here to subscribe to the magazine.
Virtual encyclopedia on modern hydronic systems.
CONNECT WITH PM ENGINEER: