Mass Management
by John Siegenthaler , P.E.
August 1, 2010
When should a solar storage tank be online vs. offline?
Several design principles apply to solar thermal combisystems. The
first, and perhaps most important, is to keep the collector inlet fluid
temperature as low as possible. This decreases heat loss from the collectors
and boosts their thermal efficiency.
A second design principle indirectly related to the first is to avoid using the
auxiliary heat source to maintain some working temperature in the solar storage
tank. Doing so delays the startup of the solar collection system when the sun
returns, and thus decreases total energy collected relative to a system
starting up with a “cooler” storage tank.
The ability to execute the second design principle depends on two
issues:
1. Does the system use the same auxiliary heat
source for both space heating and domestic water heating?
2. Does the system use the thermal mass of the storage tank
to buffer a zoned space-heating distribution system?
Let’s examine some options based on these issues.
Figure 1 shows a system that uses two auxiliary heat sources, one for space
heating and another for domestic water heating. The auxiliary heat source for
domestic water could be a standard DHW storage tank, a tankless heater or another
approved, thermostatically controlled device that can “top off” the domestic
water to the required supply temperature as necessary. The auxiliary heat
source for space heating could be a boiler or a heat pump. Its function is to
provide the heat necessary to supply the space-heating load when heat from the
solar storage tank cannot.
The solar storage tank contains a “preheating” coil for domestic water.
All cold water that will eventually be heated must pass through this coil. The
temperature rise through this coil depends on the temperature of the water in
the tank. At the end of a sunny day, the temperature at the top of the storage
tank may be high enough that the water leaving the preheating coil needs no
further temperature boost.
As it leaves the coil, the fully heated domestic water must pass through an
auxiliary water heater. However, the thermostatically controlled heating element
or burner in this auxiliary water heater would remain off. The fully heated
water from the coil is just “passing through.” It continues on the hot port of
an anti-scald-rated thermostatic tempering valve before heading to the
fixtures. This valve is an absolute
must
in any solar water-heating system or combisystem. It protects against the
possibility that water leaving the preheating coil could be very hot during sustained
sunny weather.
If a modulating tankless water heater serves as the auxiliary water-heating
device, the piping can be modified as shown in
Figure 2.
This arrangement diverts the fully heated water around the tankless heater to
avoid starting its burner, which is usually controlled by a flow switch. This
arrangement also eliminates the unnecessary heat loss that would occur by
passing heated water through the piping and other components in the tankless
heater.
Three-Way Calling
In some systems, a second three-way thermostatic valve is used for the
diverting function in lieu of a motorized valve and temperature set-point
controller. This arrangement is shown in Figure 2. It works well provided the
thermostatic diverter valve has a relatively narrow proportional operating
range. Some manufacturers now offer this dual thermostatic valve arrangement as
a preassembled module.
The three-way motorized diverting valve seen to the right of the storage tank
allows cooler water returning from the space heating distribution system (and
entering port AB of the diverter valve) to pass into the storage tank (existing
port B of the valve) or be diverted to the inlet of the auxiliary boiler
(exiting port A of the valve).
The decision on which way return flow is routed is made by an outdoor reset
controller, which measures both the temperature at the top of the storage tank
and the outdoor temperature.
This controller is set to calculate the minimum acceptable water supply
temperature for the space-heating system. If it determines the water in the
storage tank is at or above this temperature, flow is routed through the tank,
making it the heat source for space heating. If the tank’s water is not warm
enough to supply space heating, the diverter valve changes position to route
flow through the boiler. It would also close another electrical contact to
enable the boiler to operate. The same circulator that created flow through the
storage tank provides flow through the boiler.
Under this condition, the storage tank is totally isolated from the
space-heating distribution system. The tank’s temperature will continue to drop
due to flow of domestic water through the coil and heat loss through the tank’s
insulation. Assuming the tank is located in heat space — which is highly
recommended — the latter heat loss still contributes to space heating. If there
are several cloudy days in a row, the tank’s temperature will eventually
“coast” down toward room temperature. The low-grade heat leaving the tank under
such conditions is still contributing to space heating and the preheating of domestic
water.
As such, each Btu released from the tank is displacing a Btu of auxiliary
energy. When the sun re-emerges, the collector subsystem will turn on as soon
as the collectors are a few degrees warmer than the cool water at the bottom of
the storage tank. This scenario is a classic exploitation of low-temperature
heat — a
good
thing.
Flow diverting through the tank vs. the boiler also can be handled using two
“toggled” circulators as shown in
Figure 3. One circulator
operates when the tank serves as the heat source, the other when the boiler
serves as the heat source. This may be a less expensive option in larger
systems with higher flow requirements. It also allows each circulator to be
selected for the flow and head loss requirements of its respective circuit.
Efficient Design
The combisystem schematic shown in
Figure 4 uses
drain-back freeze protection of the collector array. The air space at the top
of the storage tank serves as the drain-back reservoir, as well as the system’s
expansion tank. Notice that there is no automatic make-up water subsystem. It’s
not needed. The vast majority of the water and air added during installation
remains in this
closed loop
system throughout its life. Any minor water losses through valve packings,
circulator gaskets, etc., can be monitored by the sight glass on the collector
supply pipe. Any needed make-up water can be added through the hose bib valve
in the collector piping.
This combisystem uses a single auxiliary boiler, when necessary, for
both space heating and
domestic water heating. The temperature of the water at the top of the storage
tank is continually maintained at a suitable minimum value sufficient to supply
domestic hot water when the domestic water makes a single pass through the
coil.
This arrangement eliminates the need for a separate auxiliary heater solely for
domestic hot water. It also allows the upper portion of the storage tank to
serve as a buffering thermal mass for the zoned distribution system. This is
another good thing.
The motorized diverter valve directs flow through the boiler only when
necessary to maintain the temperature of the tank. The control logic is again
based on outdoor reset control, but it is not directly (electrically) tied to
operation of the distribution system. Boiler operation is only based on
maintaining a suitable minimum temperature in the upper portion of the buffer
tank.
The compromise is that this design violates the design principle of not using
auxiliary energy to maintain the temperature of the storage tank. The key to
minimizing the influence of this compromise is good temperature stratification
in the storage tank. Such stratification will be affected by the tank’s
dimensions, as well as where the piping connections are made. The goal is to
keep the lower portion of the tank relatively undisturbed by flow and
temperature in the upper portion of the tank.
Comparing The Systems
So which approach is better? It’s hard to say. The system shown in
Figure 4 is simpler, and likely to cost less than the system in Figure 1. It
provides good buffering of the zoned distribution system, which is very
important, especially in low energy-use houses.
There are two possible ways to see if the installation cost savings associated
with the system in Figure 4 would be more than offset by slightly lower solar
energy gain due to maintaining the top of the storage tank at a minimum
temperature:
1. Build each system in the same location and at the same size. Subject each
system to identical loading. And monitor the auxiliary energy usage of each system.
2. Develop a very detailed computer
simulation model that could assess tank stratification and factor its influence
into overall system performance. I was involved in similar computer modeling
many years ago. It’s very interesting from a theoretical standpoint, but very
time consuming, and only as accurate as the assumptions used.
Neither option is a simple or an inexpensive undertaking. So, like many of the
different approaches now used in solar thermal combisystems, I suspect the
choice of systems will be made based on other factors such as available space,
desire for simplicity, the type of space-heating distribution system used, and,
perhaps most important for the customer, the capabilities, reputation and sales
skills of the firm proposing the installation. That’s also a good thing.
John Siegenthaler , P.E.
john@hydronicpros.com
Links
2009 Hydronics Know How II CD >>
Great Gift Idea!
This digital collection is a virtual encyclopedia on modern hydronic systems.
The Hydronics Know How II CD contains ALL the columns and articles John Siegenthaler has written for Plumbing & Mechanical and PM Engineer. That’s over 200 articles and columns covering everything from heat loss to hydraulic separation. Retail Price: $99.00
Visit AECStore.com for a complete description. To order by phone, call Stephanie at 248/244-1275.
Contact PM Engineer >> Send
pme your feedback by visiting our Contact Us page. View staff e-mail and mailing addresses, or send us a Letter To The Editor.
Did you enjoy this article? Click
here to subscribe to the magazine.
CONNECT WITH PM ENGINEER: