by John Siegenthaler , P.E.
April 1, 2010
The use of multiple ground source heat pumps continues to rise.
Interest in ground source
heat pumps continues to grow in North America and Europe. Although many first
learn of this technology in the context of a single heat pump used in a residential
application, there are several ways to implement multiple ground source heat
pumps in commercial systems. The most common is the use of multiple
water-to-air heat pumps served by a common “building loop” piping system as
shown in Figure 1.
In this system, each water-to-air heat pump can operate in either the heating
or cooling mode at any time. The units operating in heating extract low-grade
heat from the building loop, upgrade the temperature of that heat and deliver
it through a forced-air distribution system that serves a small area of the
building, perhaps a single room.
When a heat pump switches to cooling, it dissipates heat into the piping loop
and delivers cooled/dehumidified air via the same localized ducting.
As long as the number of heat pumps operating on cooling vs. heating allows the
building loop temperature to remain between limits of, say, 50º to 70º F, the
earth loop circulator does not need to operate. For the system shown in Figure
1, flow simply passes through the closely spaced tees without inducing flow in
the earth loop. If the building loop temperature migrates outside this
user-selected range, the earth loop circulator operates to supply the necessary
low-grade heat input or heat dissipation.
A lesser-known application involves multiple water-to-water (w/w) heat pumps
connected to an earth loop. Water-to-water heat pumps deliver their heat output
to a stream of water rather than air. The heated water can be used for loads
ranging from domestic water heating, to space heating, to snow melting.
For heating-only situations, think of a multiple w/w heat pump system as similar
to a multiple boiler system. Each heat pump represents a stage of heat
production. The number of stages operating at any time depends on the current
load.
Figure 2 shows how three heating-only w/w heat pumps
could be configured into a three-stage heat plant to serve a zoned hydronic
distribution system. A hydraulic separator is used to interface the earth loop
to the headers serving the left (evaporator) side of the heat pumps. Another
hydraulic separator interfaces the right (condenser) side headers to the
distribution system. Each heat pump has a circulator with an internal check
valve on its evaporator and condenser side. These circulators only operate when
their associated heat pump is on.
The distribution system could use individual zone circulators as shown. It also
could be designed for a single variable-speed, pressure-regulated circulator in
combination with zone valves.
Figure 3 shows a similar concept, but using zone valves and a variable-speed, pressure-regulated circulator to control flow through the heat pumps. The zone valves associated with each heat pump open only when that heat pump is operating. The speed of each pressure-regulated circulator changes as necessary to maintain a constant pressure differential across the headers as the zones’ valves open and close. This configuration will reduce circulator energy use relative to the configuration shown in Figure 2, especially if high-efficiency ECM-based circulators are used.
As is true with a multiple boiler system, the greater the number of stages, the better the match between heat output and the load. Figure 4 shows how a four-stage w/w heat pump system, where each heat pump represents 25% of the design load, would operate to handle a hypothetical load profile.
Many w/w heat pumps come with internal reversing valves that allow them to operate as either a hydronic heat source or a chiller. When the internal reversing valve is not energized, the unit operates as a heat source. When the reversing valve is powered on by a 24 VAC signal, the previous functions of the evaporator and condenser are reversed and the unit delivers chilled water.
When there is a simultaneous demand for both heating and cooling, the
w/w heat pump shown at the bottom of the schematic operates in “double duty.”
It extracts low-grade heat from the chilled water buffer tank and dissipates
that heat, along with the heat generated by its compressor, into the heated
water buffer tank. This heat pump operates at a very high “effective” COP
considering that the electrical energy used by a single compressor produces
both heating and cooling capacity. Any supplemental heating or cooling required
to maintain the buffer tanks within acceptable temperature limits is handled by
the upper group of heat pumps operating in whatever mode is
required.
All indications are that ground source heat pump systems will continue to gain
market share in both residential and commercial applications. It behooves HVAC
designers, especially those dealing with hydronic heating and cooling systems,
to know how to apply their unique characteristics.
John Siegenthaler , P.E.
john@hydronicpros.com
Did you enjoy this article? Click here to subscribe to the magazine.
Virtual encyclopedia on modern hydronic systems.
CONNECT WITH PM ENGINEER: