by Robert H. Thompson, CIPE
October 5, 2006
To conclude this article, the author discusses design points on the fire pump curve—and provides tips for reducing shut-off pressures and system layout.

The required discharge head, whether expressed in feet of head (ft.) or pounds per square inch (psi), is the pressure that is required to produce the sum of:
The required residual pressure varies with the codes in question. For example, the requirements are 25 psi in New York, 65 psi in Chicago and 100 psi for the International Building Code and International Fire Code. The 100 psi requirement appears in NFPA 14, the Standpipe Installation Standard.
The piping design layout influences the frictional losses. The Building Code may dictate requirements for the piping layout, especially as the building’s overall height increases, resulting in the need for multiple zones.
For example:
Figure 2. New York requires a roof tank on buildings higher than 300 feet and an additional manually controlled fire pump.
This is the design point on the pump curve that is normally used to select and specify the fire pump model and the horsepower.
NFPA 20 prescribes two additional points that must be met on the fire pump curves.
All fire pumps listed for fire protection service must have performance curves that meet these three curve conditions. Fire pumps are generally selected within a range of 90% to 130% of the primary rating point of a given pump capacity. As an example, a 750-gpm pump might be selected and utilized for a demand of between 675 gpm and 975 gpm, but once the primary rating point of the next size pump is reached, the larger pump should be selected.
Once a fire pump is selected from a specific manufacturer’s curve, other important system design points can be evaluated. Plotting the fire pump’s performance curve on a graph of the project’s water flow test data allows for the prediction of the system’s maximum churn pressure.
According to NFPA 20, the “Shut-Off”condition pressure, plus the water supply static pressure, should not exceed 175 psi for single-zone sprinkler/standpipe systems and 350 psi in multiple-zone systems.
Figure 3. NFPA 14 requires 4" minimum diameter standpipes and 6" minimum diameter combined sprinkler/standpipes be connected by a common bulk main from the fire pump at the lowest level.
2. Select a fire pump model that has 20% or less rise to shut-off, not 40%.
3. Consult the manufacturer’s representative to determine if the model with the lowest rise to shut-off is being specified. Trimming the impellers may reduce the rise to shut-off further. Only certain manufacturers and models may benefit from trimming, with some having a rise to shut-off as low as 5% above the system’s required duty point.
4. If two fire pumps are piped in series for the high zone, determine whether the high zone pump can meet the zone requirement by taking suction directly from the residual city water main in parallel. This avoids adding two rise to shut-off pressures to the water supply static pressure.
5. Increase the system pipe sizes to reduce the friction loss in the system.
6. Consult the fire pump controller manufacturer regarding the use of a “variable speed controller” to electronically reduce the pump’s rise to shut-off. This method produces a similar result to trimming the impeller and can be used with any pump model or manufacturer.
Remember, fire pumps are manufactured in a range of capacities and styles, each offering their own benefits and drawbacks in terms of costs, system layout and hydraulic design.
Popular configurations are:

Some suggested tips:
Following these design considerations will result in plans and specifications that are easily understood. This will assist in expediting the project during plan review, as well as reduce any possibility of costly design revisions.
Early sprinkler/standpipe systems had only upright, pendent or horizontal sidewall sprinklers. The piping system was Schedule 40 steel pipe with threaded or flanged 125-pound valves and fittings. These 125-pound fittings were installed in systems that had a maximum pressure of 175 psi. For systems having a pressure in excess of 175 psi, extra heavy 250-pound valves and fittings were installed. Extra heavy fittings were considered acceptable for systems having a maximum pressure of 400 psi.
What is often forgotten is that the125-pound and 250-pound designations were a “nominal class rating.” This indicated that the maximum service pressure of the valves and fittings was established at the temperatures’ saturated steam.
If you review the valve or fitting manufacturer’s rating chart, the pressure rating determined at the water service temperature of 150ºF for a sprinkler/standpipe systems shows a 125-pound class fitting equates to 175 psi maximum pressure. Likewise, a 250-pound class fitting equates to a 400 psi maximum system pressure.
Hence, the industry has maintained the 175 psi as a rating pressure for the testing and listing of sprinkler components.
Does this mean that a failure may occur if the rated pressures are exceeded? Not really. The maximum pressure of listed sprinkler components is used by testing agencies to establish a common point for evaluation.
Sprinkler and standpipe components are further tested to provide an additional safety factor of 2.5 times the listed pressure for leakage and five times before burst.
The degree to which the design exceeds the rated pressure of sprinkler components reduces the safety factor. This becomes the discretion and judgment of the engineer/designer. The engineer should consult with their firm’s risk management officer regarding the advisability of such a design. Of course, the authority having jurisdiction must approve the design. A water damage lawsuit from a single, failed sprinkler component that was exposed to pressures exceeding the rated pressure of the component will be costly to defend.
Fire pump tests normally start with the fire pump running at the churn condition while pressure and motor readings are being recorded. Then the 2-1/2-inch fire department valve outlets are opened to show and document the readings at the primary and secondary rating points. The pump is slowly brought back to churn condition by closing the 2-1/2-inch fire department valve outlets.
If all parts of the test were normal, the system is then switched into automatic mode of operation for its intended service. Remember, any sprinkler/standpipe system designed to churn in excess of the maximum listed pressure of the sprinkler component installed will be exposed to this higher pressure during the operational life of the system. The pressure will only be lowered for testing and maintenance.
Robert H. Thompson, CIPE
mailto:rthompson@mehandeseng.com
Robert H. Thompson, CIPE, has nearly 40 years of plumbing and fire protection design experience and has led design teams of prestigious consulting engineering firms. He is the plumbing and fire protection director at Mehandes Engineering P.C., a MEP/FP engineering firm that specializes in commercial and high-rise residential projects.
Thompson pioneered the design of centralized hot water supply and recirculation systems for high-rise buildings that is the arrangement of choice in the Chicago area. His e-mail address is rthompson@mehandeseng.com.
Did you enjoy this article? Click here to subscribe to the magazine.
Virtual encyclopedia on modern hydronic systems.
CONNECT WITH PM ENGINEER: