Cover Story
Chilled Beams Get A Warm Reception
by Greg Cunniff , P.E.
August 1, 2010

Wellington Mechanical Group’s Alex Hof works on a chilled
beam system. Photo by Andre Van Vugt.
Buildings in Chicago and Toronto benefit from this straightforward technology.
Tracing radiant technology’s genealogy, a
new member of the family recently entered our consciousness: chilled beam
radiant cooling. With chilled beam systems, chilled water circulates through
tubing embedded in a metal ceiling fixture to wick away
heat.
What makes this technology so interesting is its broad applicability for
commercial structures and extreme energy and thermal efficiency. A key advantage
is that a chilled beam system requires very little ceiling space and height,
or, in the parlance of commercial architects and designers, it conserves
interior real estate.
Another key advantage, functionally and financially, is that water — the main
transporter of thermal energy and much denser than air — permits a very high
energy- carrying capacity and a smaller transport system: pipes. A forced-air
system is, by its very nature, greatly less efficient because of the inherently
low density of air and requires large ducts to transport Btu.
Chilly In The Windy City
Enlarge this
picture
Active chilled beams were installed as part of a renovation
to an office tower in Chicago.
The structure located at 250 S. Wacker Drive in downtown Chicago is a
15-story, multitenant office tower with retail space on the first floor. The
first and top floors had dedicated HVAC systems separate from systems serving
the second through 14th floors. These intermediate floors had a
floor-mounted induction perimeter system and a constant volume-variable
temperature interior system. Each of the floors had about 14,300 square feet of
rentable floor area (215,000 square feet total).
A major renovation of the building included removal of the building’s exterior
walls and glass, and gutting of the structure down to the concrete. Building owners
concluded the existing induction units and enclosures would have to be
replaced.
Fortunately, the renovation involved a change to 100% low-e exterior glass,
which significantly reduced the building’s heating and cooling loads. Heat
losses along the perimeter were reduced to less than 200 Btu/lineal foot, which
made it possible to provide comfort conditioning of interior spaces with active
chilled beams mounted overhead.
Jim Wilson of
Windy City Representatives, a Chicago HVAC manufacturers rep firm, says many
advantages have been realized, beginning with unobstructed visibility through
the floor-to-ceiling windows along all exterior walls. Also, there are no
downdrafts and floor space has been gained, while the cost of custom enclosures
for floor-mount units was avoided. Finally, fan energy and noise levels have
been greatly reduced.
The Ultimate Integration
Let’s delve into the chilled beam concept a little further. Because
chilled beams are ceiling-mounted and do not use drain pans, the chilled water
supply temperatures must be above the ambient dew point. As a result,
dehumidification, or latent cooling, is handled by a separate 100% dedicated
outdoor air system (DOAS) supplying dry, conditioned air to the space.
Passive chilled beams employ natural convection, while active chilled beams
employ forced convection. Passive chilled beam systems supply the DOAS airflow
through a separate diffuser or grille in the room. An active chilled beam
supplies the DOAS airflow through the chilled beam, thereby increasing the
capacity of the cooling coil through forced convection.
The amount of outside air required to operate a typical chilled beam system is
much less than that needed for a forced-air system. A chilled beam system
typically needs only one air change per hour, using outside air to pressurize
the space to prevent the infiltration of outside air. With a forced-air system,
that need grows to eight to 10 air changes of recirculated (and fresh) air to
cool a space.
Also reduced is the ceiling space typically required for ductwork. The amount
of air circulated by the central system is also dramatically reduced, often 80%
to 90% less than with conventional, all-air systems. Of course, this dramatically
reduces the horsepower to circulate air within interior
spaces.
The net result is lower energy consumption and operating costs. Studies have
shown — in typical U.S.
commercial buildings — that fan energy is often second only to lighting in energy
consumption. With active chilled ceiling and chilled beam systems, energy to
operate fans is dramatically reduced due to the relatively small amount and low
pressure of the primary air being circulated by the central system.
Figure
1 shows that a radiant cooling/chilled beam system can reduce
electrical energy demand by almost 25%.
Beam Me Up
Chilled beams sound futuristic, but many
trade professionals are surprised to learn the technology is relatively simple
and straightforward.
In a radiant chilled ceiling system, 50% to 60% of the heat transfer from a
chilled panel is radiant, while 40% to 50% is convective (as shown in
Figure
2).
The chilled water temperature must be above dew point to prevent condensation
from forming on the underside of the panels. This is typically in the range of
55 to 60 degrees F. The driving force or temperature difference between the
chilled water and a room at 75 degrees F is therefore reduced, falling within
the range of 15 to 20 degrees F as opposed to a conventional chilled water
system using 40 to 45 degrees F chilled water and a range of 30 to 35 degrees F
temperature difference.
As a result, higher chilled water flow rates are required to achieve reasonable
capacities. These flow rates are in the range of 4.5 to 6 gpm per ton using
chilled water delta Ts of 4 to 5 degrees F as opposed to conventional chilled
water systems of 2 to 3 gpm per ton using delta Ts of 8 to 12 degrees F as
shown in Figure 2. The chilled water flow rate for chilled panels and ceilings
is therefore approximately double that of conventional chilled water
systems.
Even with higher flow rates, the capacity of radiant chilled panels and
ceilings is relatively low — in the range of 2 to 40 Btuh/sq. ft. While this is
within the range of cooling loads for interior spaces, it may not be adequate
for interior spaces with exterior walls. For the European experience in the
1980s, some cooling was better than none.
The Europeans discovered from their experience that by lowering the chilled
panel below the ceiling that the convection cooling component of the individual
panels could be increased. This satisfied the increased cooling loads from the
increased use of computers seen in the 1990s. There also was a desire to
provide higher cooling capacities for exterior zones to provide better overall
comfort.
By lowering the panel below the ceiling and making it an open coil, as shown in
Figure 3, the capacity of the chilled panel can be increased
to 120 to 150 Btuh/sq. ft. The industry has designated this configuration a
“passive chilled beam.” It resembles a beam when mounted below the ceiling. It
is passive since the convective cooling component is natural convection.
Passive Vs. Active
Chilled beams are available in three variations: passive, active and
integrated/multiservice beams. The difference between passive and active beams
focuses on the way airflow and fresh air are brought into the space. Both of
these systems are now enjoying significant attention here.
Passive chilled beams require
ventilation air to be delivered by a separate air-handling system. With active chilled beam systems — sometimes
referred to as “induction diffusers” — a building's ventilation air is
continuously supplied to chilled beam terminal units by a central air-handling
system.
Ventilation air is cooled or heated to partially handle temperature-driven
sensible loads, while in the summer it is sufficiently cooled and dehumidified
to handle all of the internal moisture-driven latent loads. With active chilled
beams, air from the chilled beam is introduced into the space through a slot
diffuser, creating a Coanda effect: the tendency of a fluid jet to be attracted
to a nearby surface or, in this case, the ceiling.
Inducing warm room air to blow through the chilled coil substantially increases
the capacity of the chilled beam. Active chilled beam capacities are in the
range of 350 to 600 Btuh/sq. ft. for the coil. Added to this is the capacity of
the primary air from the DOAS. Depending on the temperature and quantity of
this primary supply air, this can add up to 300 Btuh/sq. ft. of capacity. An
active chilled beam can deliver from 500 to 900 Btuh/sq. ft. between the
chilled coil and the primary air (see a chilled beam
configuration in
Figure 4).
Primary/ventilation air is introduced into the active chilled beam
through a series of nozzles. This induces room air into the chilled beam and,
in turn, through a water coil. Induced room air is cooled and/or heated by the
water coil and then mixed with ventilation air and released, which controls
room temperature.
The technology works in tandem with a central air system, which is calibrated
to circulate only the amount of air needed for ventilation and latent load purposes.
The chilled beams provide the additional air movement and sensible cooling
and/or heating required through the induced room air and secondary water
coil.
With an active beam, ventilation air is delivered to the beam by a central air
system through ducts. The beam unit itself, then, is not unlike an induction
unit turned upside down, mounted to the ceiling. Ventilation air moves through
ductwork, forcing room air to make contact with the cooling coil. This air then
mixes with the primary ventilation air and delivers it through linear
diffusers.
Linear slot diffusers have been used for a number of years in variable air
volume systems. Their primary advantage is that they don’t “dump” cold air at
low flow rates, making occupants uncomfortable.
It’s in this way that chilled beams transfer a huge portion of cooling (or
heating) loads from the less efficient air distribution system to the greatly
more efficient water distribution system.
Northern Exposure
Enlarge this
picture
Chilled beam technology has developed into an alternative to
conventional variable air volume systems.
In 2008, Taco constructed a new manufacturing plant and office in
Milton, Ontario (outside Toronto). Taco wanted to use the facility to
demonstrate the latest advanced hydronic systems that the HVAC industry has to
offer. This included new radiant cooling and chilled beam technology as well as
conventional fan coils and baseboard heating.
The building’s existing space was renovated for this new application and
included installing new insulation and double-pane windows, which significantly
reduced the heating and cooling loads, the size of the mechanical system and
energy costs. Further cost reduction resulted from the chilled beam and chilled
ceiling systems.
Active chilled beams were used in the training areas as well as general office
areas. Chilled ceilings were used to supplement the chilled beams in the
training areas.
The chilled beams and chilled ceilings reduce fan energy by a factor of 10,
since the only air circulation required is from a 100% DOAS. This system supplies
just enough treated, dehumidified outdoor air to slightly pressurize the
building, negating natural infiltration of humid outside
air.
The amount of fresh air supplied to the building is controlled by a
differential pressure sensor measuring the difference in static pressure
between the building and the outside. This sensor and accompanying DDC
controller then control the speed of the DOAS unit fan to maintain this slight
positive pressure. Fan coils were used at the entrances to overcome the inrush
of humid air that overwhelms the slight building positive pressure when a door
is opened.
With a better thermal envelope for the building, the chilled beams and chilled
ceilings can be used for heating without supplemental heat almost everywhere in
the building. Again, the use of fan coils at entrances overcomes the inrush of
cold air in the winter when a door is opened. Some baseboard was used in
offices that had large windows, which were not reduced in size during the
renovation to limit possible drafts.
The use of these different terminal units requires different supply water
temperatures throughout the building. This would typically result in four
piping systems and eight pipes for high-temperature chilled water (chilled
beams), low-temperature chilled water (fan coils, DOAS), high-temperature
heating water (baseboard, fan coils, DOAS) and low-temperature heating water
(chilled ceilings, chilled beams).
Using Taco’s single-pipe LoFlo system, the piping was reduced to two pipes —
one pipe carries low-temperature chilled water and one pipe carries
high-temperature heating water. In addition, these pipes are smaller than a
conventional system’s pipes. The LoFlo Mixing Block contains an injection pump
that mixes up low-temperature chilled water to high temperature where required,
and mixes down high-temperature heating water to a lower temperature where
required.
As more systems are installed in North America, chilled beam technology has
developed into an alternative to conventional variable air volume systems.
Injection Mixing Systems
Taco has
introduced technology to help radiant cooling/chilled beam systems achieve
energy savings.
Although
radiant cooling and chilled beams reduce fan electrical energy demand and
consumption up to 10 times from an all-air HVAC system, the pump energy demand
doubles. Now if the pump energy could be reduced, then a radiant
cooling/chilled beam system could achieve significant energy savings.
Taco’s new, award-winning LOFlo® injection mixing
system accomplishes this. Injection
pumping has been used for a number of years in radiant heating systems by
mixing down the higher temperature boiler water (at 180 degrees F) to that
needed for a radiant floor panel (100 degrees F to 120 degrees F). This same
principal can be applied to a radiant cooling system, only in reverse—to mix up
low temperature chilled water (40 degrees F to 45 degrees F) to that required
by a chilled ceiling panel or beam (55 degrees F to 60 degrees F).
Shown in
Figure 5 is a schematic piping
layout for a radiant cooling/chilled beam, low flow/low temperature injection
piping system. In this system, instead of the primary chilled water flow being
double that of a conventional chilled water system, it requires only
one-quarter of the flow. This is the case since the primary chilled water
system temperature difference is now 16 degrees F instead of a radiant
cooling/chilled beam system of 4 degrees F and a conventional system of 8
degrees F.
This system reduces the electrical energy demand of an all-air system by
almost 30 % or more, thus reducing the transport energy to only 20 % of the
total HVAC system. This system, recently introduced by Taco, promises to be one
of the most efficient HVAC systems to become available on the U.S. market. It
combines hydronic heating and cooling energy transport with injection radiant
heating and cooling energy delivery in the conditioned space.
Taco’s new LOFlo® Mixing Block is a prepackaged unit
consisting of a variable speed injection circulator and constant-speed zone
circulator. The variable-speed injection circulator is controlled by a sensor
that monitors incoming water temperature to a radiant panel (floor, wall or
ceiling) or chilled beam (ceiling). The constant-speed zone circulator is
controlled by the room thermostat.
Greg Cunniff , P.E.
Greg Cunniff is the manager
of application engineering for Taco. He holds a master’s degree in aerospace
and mechanical engineering from Montana
State and is a licensed professional
engineer in California, Florida
and Montana.
Links
Contact PM Engineer >> Send
pme your feedback by visiting our Contact Us page. View staff e-mail and mailing addresses, or send us a Letter To The Editor.
Taco >> www.taco-hvac.com
Did you enjoy this article? Click here to subscribe to the magazine.
CONNECT WITH PM ENGINEER: