by John Siegenthaler , P.E.
May 1, 2009
Consider their many attributes, which are well-suited to address concerns about a building’s operational cost and environmental impact.
As 2009 unfolds, there are many concerns about
how the HVAC industry, especially the portion associated with new construction,
will fare in the months (years?) ahead. America appears to have reached a point
where a retracting economy and unstable energy prices have driven building
owners to reexamine priorities.
The frills and energy-related complacency that were more easily absorbed in
construction budgets only a few years ago are giving way to pragmatic choices
about the efficacy of the building, its appeal to future tenants, its long-term
impact on the environment, and its cost of operation.
One technology benefiting from this reexamination of priorities is geothermal
heat pump systems. Although certainly not new in the HVAC industry, these
systems offer a set of attributes that makes them well suited to the current
situation:
1. They can be
quickly switched from heating to cooling or vice versa as the needs of the zone
change.
2. In commercial
buildings, they take advantage of load diversity (e.g., a common situation in
commercial buildings in which there are simultaneous demands for heat and
cooling in different zones).
3. Their efficiency, in well-matched applications, lets them
deliver heat at a unit cost that’s significantly lower than provided by other
fuel options.
4. They harvest the
majority of their heating energy from “phase delayed solar energy” (e.g., solar
heat stored in the earth for several months), and, thus, can legitimately be
classified as a renewable energy system. Congress recently made this “official”
through wording in the economic stimulus legislation.
5. They are
complementary to electrical energy produced by clean-energy sources such as
photovoltaic systems, wind power and hydropower.
6. Since they only
require electricity as a “fuel,” they lend themselves to evolving electrical
procurement and demand side management strategies such as time-of-use rates,
real time pricing, and “smart grids.”
7. They can “amplify”
the efficiency of a combined heat and power generator driven by natural gas,
propane, or biofuels.
8. They are well
matched to low-temperature heating loads such as radiant floors and domestic
water heating (or preheating).
9. They create virtually zero on-site emissions.
The lower temperature “source” water for a geothermal heat pump system can come from a variety of sources:
Once inside the building, the system typically transitions to rigid piping materials, including steel, CPVC, and polymer composites. Flow passes through standard equipment such as an air/dirt separator and redundant “lead/lag” circulator set. The distribution piping within the building is usually constructed as a reverse return loop located in overhead mechanical plenum, as shown in Figure 2.
In most commercial GSHP systems, any heat pump
on the distribution system can operate in the heating or cooling mode at any
time, depending on the needs of its zone. This is beneficial in larger
buildings that often require cooling of interior zones, even in winter, while
perimeter zones operate in heating mode.
Water temperature in the building loop increases as the heat of rejection from
heat pumps operating in cooling exceed the heat of absorption for units
operating in heating. In winter, this tends to keep the building loop slightly
warmer, which improves the performance of heat pumps operating in heating. In
summer, when all heat pumps are cooling, building loop temperature will rise
significantly. Designers must ensure the ground loop is adequately sized to
dissipate this heat. Maximum heat rejection is often the controlling factor in
sizing ground loops for commercial projects.
The “extended range” heat pumps now used in commercial geothermal systems are
capable of operating at incoming source fluid temperatures down to the mid 20ºF
range. In Northern climates, where systems operate in heating-dominated
conditions for several months, designers must evaluate the ground heat
exchanger for minimum operating temperature. This temperature might even be a
few degrees below 32ºF, and, thus, the ground loop (and perhaps the building
loop as well) would need to operate with an antifreeze solution.
Under such conditions, the surface of the building loop piping could drop below
the dewpoint of the interior air, and condensation would form. In such situations,
the interior distribution system piping should be insulated and vapor sealed.
The lower thermal conductivity of polymer and composite tubing makes it less
prone to surface condensation relative to metal piping. However, every system
should be evaluated for specific materials and operating conditions when
determining if interior piping insulation is necessary.
Other design options for commercial GSHP systems include layouts where each building zone is equipped with one to three heat pumps. These units are then connected to vertical U-tube heat exchangers in boreholes located directly outside that space. An example of this concept is shown in Figure 4.
With ECM-based variable speed circulators now
available in North America, look for even more optimized hydraulics on
commercial GSHP systems. An example is use of 2-way on/off zone valves that
close off a branch flow path through an inactive heat pump and allow the circulator
to settle to a lower speed and lower power consumption.
A related option is using a modulating valve to maintain a specific temperature
change across the heat pump evaporator or condenser of each heat pump. We will
discuss these and other new options for commercial GSHP systems in more detail
in Part 2.
John Siegenthaler , P.E.
john@hydronicpros.com
Did you enjoy this article? Click here to subscribe to the magazine.
Virtual encyclopedia on modern hydronic systems.
CONNECT WITH PM ENGINEER: